Free tool

What fire inspections does your building need, and when?

Tell us which fire protection systems your building has. You'll get a dated schedule of every required inspection and test, who's allowed to do each one in your state, and licensed contractors nearby.

Which systems does your building have?

Dates are optional but make the schedule exact. Find them on the service tags or your last inspection report.

Inspection frequency reference

Baseline intervals from the NFPA standards most jurisdictions adopt. Your local fire marshal has final say on editions and local amendments.

Wet pipe sprinkler system · NFPA 25 · Fire sprinkler contractors

FrequencyTaskWhoDetails
MonthlyControl valve checkYour staffConfirm control valves are open and locked or supervised. Sealed (unlocked, unsupervised) valves need weekly checks.
QuarterlyQuarterly inspectionLicensed contractorGauges, alarm devices, waterflow alarms, fire department connection and signage.
AnnualAnnual inspection and testLicensed contractorFull inspection of sprinklers, pipe and hangers, main drain test, valve operation and alarm tests.
Every 5 yearsInternal pipe assessmentLicensed contractorOpen the system to check for obstructions and corrosion. Also replace or recalibrate gauges every 5 years.
By age or typeSprinkler sample testingLicensed contractorStandard-response sprinklers are sample-tested or replaced at 50 years, fast-response at 20 years.

Dry pipe or preaction sprinkler system · NFPA 25 · Fire sprinkler contractors

FrequencyTaskWhoDetails
QuarterlyQuarterly inspectionLicensed contractorAir pressure, gauges, alarm devices and valve condition.
AnnualAnnual trip testLicensed contractorPartial trip test of the dry pipe valve every year; a full-flow trip test every 3 years.
AnnualDrain condensate before freezing weatherLicensed contractorDrain low points (auxiliary drains) before the freezing season and as needed after.
Every 5 yearsInternal pipe assessmentLicensed contractorCheck for obstructions and corrosion; dry systems are especially prone to it.
Every 10 yearsDry sprinkler testingLicensed contractorDry-type sprinklers are sample-tested or replaced every 10 years.

Fire pump · NFPA 25 · Fire sprinkler contractors

FrequencyTaskWhoDetails
MonthlyNo-flow (churn) testYour staffRun the pump without flowing water: weekly for diesel pumps, monthly for most electric pumps.
AnnualAnnual flow testLicensed contractorFull-flow performance test compared against the pump's rated curve.

Standpipe system · NFPA 25 · Fire sprinkler contractors

FrequencyTaskWhoDetails
AnnualAnnual inspectionLicensed contractorHose connections, valves, piping and signage.
Every 5 years5-year flow or hydrostatic testLicensed contractorFlow test for automatic and semi-automatic standpipes; hydrostatic test for manual and dry standpipes.

Backflow preventer on the fire line · NFPA 25 and local water utility · Fire sprinkler contractors

FrequencyTaskWhoDetails
AnnualAnnual backflow and forward flow testSpecialistUsually done by a certified backflow tester; many sprinkler contractors have one. Your water utility may set its own deadline.

Fire alarm system · NFPA 72 · Fire alarm companies

FrequencyTaskWhoDetails
AnnualAnnual inspection and testLicensed contractorTest initiating devices, notification appliances, the control panel, batteries and monitoring connection.
Every 2 yearsSmoke detector sensitivity testLicensed contractorWithin a year of installation, then every 2 years (up to 5 if results stay within range).

Portable fire extinguishers · NFPA 10 · Fire extinguisher companies

FrequencyTaskWhoDetails
MonthlyMonthly visual checkYour staffConfirm each extinguisher is in place, charged (gauge in the green), unobstructed and tagged. Record the date.
AnnualAnnual maintenanceLicensed contractorFull maintenance and new service tag by a licensed company.
Every 6 years6-year internal maintenanceLicensed contractorFor stored-pressure dry chemical extinguishers that require a 12-year hydrostatic test.
By age or typeHydrostatic testLicensed contractorEvery 5 years for water, CO2 and wet chemical (Class K) units; every 12 years for dry chemical.

Kitchen hood suppression system · NFPA 17A and NFPA 96 · Fire extinguisher companies

FrequencyTaskWhoDetails
SemiannualSemiannual inspection and serviceLicensed contractorInspect and test the system and replace fusible links.
SemiannualHood and duct cleaningSpecialistInterval depends on cooking volume: monthly for solid fuel, quarterly for high volume (24-hour, charbroiling, wok), semiannual for moderate, annual for low volume. Done by a hood cleaning company.
Every 12 yearsCylinder hydrostatic testLicensed contractorAgent cylinders are hydrostatically tested every 12 years.

Emergency and exit lighting · NFPA 101

FrequencyTaskWhoDetails
MonthlyMonthly 30-second testYour staffSwitch each unit to battery for at least 30 seconds and record the result.
AnnualAnnual 90-minute testYour staffRun each unit on battery for 90 minutes. Often done by an electrician or fire alarm company.

Frequently asked questions

How often does a commercial fire sprinkler system need to be inspected?
Under NFPA 25, wet pipe sprinkler systems get quarterly inspections of gauges and alarm devices and a full annual inspection and test by a licensed contractor, with an internal pipe assessment every 5 years. Control valves are checked monthly (weekly if they are only sealed). Your local fire marshal may require more.
How often does a fire alarm system need to be tested?
NFPA 72 requires most fire alarm devices, the control panel and batteries to be inspected and tested annually, and smoke detector sensitivity to be tested within a year of installation and then every 2 years.
How often do fire extinguishers need service?
Under NFPA 10, staff should visually check each extinguisher monthly, a licensed company must do annual maintenance, stored-pressure dry chemical units need 6-year internal maintenance, and hydrostatic tests are due every 5 or 12 years depending on the type.
How often does a restaurant hood suppression system need service?
Kitchen hood suppression systems need inspection and service every 6 months under NFPA 17A and NFPA 96, including replacing fusible links. Hood and duct cleaning runs from monthly to annually depending on cooking volume.
Is this schedule legally binding?
No. It is a baseline drawn from the NFPA standards most jurisdictions adopt. Your local fire marshal (the authority having jurisdiction) decides which editions and amendments apply, and insurers or manufacturers can add requirements.

Sources: NFPA 25 (water-based systems), NFPA 72 (fire alarm), NFPA 10 (extinguishers), NFPA 17A and 96 (kitchen hood systems), NFPA 101 (emergency lighting). General guidance, not legal advice. Machine-readable: Markdown.